<cite id="rpnrr"></cite>

        <pre id="rpnrr"></pre>

        <pre id="rpnrr"></pre>

        Welcome.....
        13609154326
        • TEL:13609154326(Mr.Wang)
        • QQ:1832126906
        • E-mail:1832126906@qq.com

        High voltage switch cabinet

        KYN28A-12 series of indoor metal armored switch cabinet

          Summary  

        KYN28A-12 series of indoor metal armored switch cabinet is set for 3.6~12KV three-phase AC 50Hz single busbar and single busbar system, mainly used in power plant, generator power transmission, power distribution and power system of industrial and mining enterprises of the two substations, power transmission, large high voltage motor starting so, the implementation of measurement, control, protection and monitoring purposes, the cabinet to meet the IEC298, GB3906 and other standards, can prevent the load push-pull circuit breaker, prevent mistakenly charged isolation room, prevent chain function when energized by close grounding switch, can be used with ZN63A or VSK (VS1) vacuum circuit breaker, can VD4 vacuum circuit breaker with ABB and VSM, permanent magnetic circuit breaker series is a superior performance of power distribution equipment.

        blob.png

          Characteristic  

        1. the shell adopts imported tibnor, with CNC machining, the multi folding technology, assembly by assembly of international popular, the cabinet has high precision, light weight, high mechanical strength, beautiful appearance, high degree of enclosure protection, up to IP4X;

        2. the main electrical components of the switchgear have an independent compartment, the protection level between the compartments is IP2X, the handcart room, the bus room and the cable room all have special pressure relief channels. The cable room has a large space and can be connected with multiple cables.

        3. the plan is complete, with the overhead line of import and export, the cable import and export line and other plans, after the arrangement and combination, it can meet all kinds of power supply and distribution requirements of the users.

        4. The repair mode in front of this switchgear can make the product be installed back to back or by wall, saving the area, and the post maintenance mode is easy to operate and maintain.

        5. All kinds of anti error operation are complete, flexible, safe and reliable.

        6. A high voltage live display device and an anti condensation heater can be installed according to the requirements of the user.

        7. The handcart is assembled by CNC machine tool with thin steel plate. The mechanism is flexible, reliable, excellent in performance and easy to operate. The same specifications are completely interchangeable.


        Main parameter

        Name

        Unit

        Data

        Rated voltage

        kV

        3.6,7.2,12

        1min power frequency withstand voltage (effective value) phase, phase / break

        kV

        42/48

        Lightning impulse resistance (peak)

        kV

        75

        Rated frequency

        Hz

        50

        The main busbar rated current

        A

        630,1250,1600,2500,3150,4000,5000

        Branch bus rated current

        A

        630,1250,1600,2000,2500,3150,4000

        Rated short circuit breaking current

        kA

        20,25,31.5,40,50

        Rated heat stable current / time

        kA/s

        20,25,31.5,40,50/4

        Rated dynamic stable current (peak value)

        kA

        50,63,80,100,125

        Rated short-circuit closing current

        kA

        50,63,80,100,125

        Protection grade

        -

        IP4X

        Weight

        kg

        about900


        Appearance diagram


        blob.png


        Order demand for switch cabinet

        1. The standard book for the user's order:

        A, one line system diagram and plane layout.

        B, rated voltage of one line, rated current and use of each cabinet;

        C, two circuit schematic diagram;

        D, the detailed specifications and quantity of each electrical equipment;

        2. the main bus specifications and materials;

        3. The list of spare parts and spare parts which need to be added outside the complete set of products;

        4. bus bridge (two column cabinet and bus bridge between StorWall bus bridge) is required to provide the span and height dimensions;

        5. The use of switchgear in special environmental conditions should be put forward at the time of order.

        6. if the user has special requirements, please consult with us to solve it.